EDR-3000 IM02602003E
Parameter Description Setting range Default Menu path
Inverting 6 Inverting of the state of the assigned signal. Inactive,
Active
Inactive [Device Para
/Relay Outputs
/RO-3ZI X2
/RO 3]
Assignment 7 Assignment 1..n, Assignment
List
-.- [Device Para
/Relay Outputs
/RO-3ZI X2
/RO 3]
Inverting 7 Inverting of the state of the assigned signal. Inactive,
Active
Inactive [Device Para
/Relay Outputs
/RO-3ZI X2
/RO 3]
DISARMED Ctrl Enables and disables the disarming of the relay outputs.
This is the first step of a two step process, to inhibit the
operation or the relay outputs. Please refer to
"DISARMED" for the second step.
Inactive,
Active
Inactive [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-3ZI X2]
Disarm Mode CAUTION! RELAYS DISARMED in order to safely
perform maintenance while eliminating the risk of taking
an entire process off-line. (Note: Zone Interlocking and
Supervision Contact cannot be disarmed). YOU MUST
ENSURE that the relays are ARMED AGAIN after
maintenance.
Permanent,
Timeout
Permanent [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-3ZI X2]
t-Timeout DISARM The relays will be armed again after expiring of this time.
Only available if: Mode = Timeout DISARM
0.00 - 300.00s 0.03s [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-3ZI X2]
Force Mode By means of this function the normal Relay Output States
can be overwritten (forced) in case that the Relay Output
is not in a disarmed state. The relays can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state.
Permanent,
Timeout
Permanent [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-3ZI X2]