EDR-3000 IM02602003E
Definitions
Time to Trip: Time between First Alarm (Prot.Pickup) and First Trip (Prot.Trip) decision
Fault Duration:
Time period from the rising edge of the General Pickup (»PROT.PICKUP«) signal up to the falling
edge of the General Pickup Signal. Please note that General Pickup is an or-connection
(disjunction) of all Pickup signals. General Trip is an OR-connection of all Trips.
www.eaton.com 223
Prot.Pickup
Signal: General Pickup
t
t
0
1
0
1
Time to trip
t
0
1
Analog values (recording)
0
0
t-meas-delay>0
Popup pops up on the display.
t-meas-delay=0
Fault duration
0
Capture Data
Capture Data
Prot.Trip
Signal: General Trip