EDR-3000 IM02602003E
Signals of the SNTP
Signal Description
SNTP active Signal: If there is no valid SNTP signal for 120 sec, SNTP is regarded as inactive.
SNTP Counters
Value Description Default Size Menu path
NoOfSyncs Total Number of Synchronizations. 0 0 - 9999999999 [Operation
/Count and RevData
/TimeSync
/SNTP]
NoOfConnectLost Total Number of lost SNTP Connections (no sync
for 120 sec).
0 0 - 9999999999 [Operation
/Count and RevData
/TimeSync
/SNTP]
NoOfSmallSyncs Service counter: Total Number of very small Time
Corrections.
0 0 - 9999999999 [Operation
/Count and RevData
/TimeSync
/SNTP]
NoOfNormSyncs Service counter: Total Number of normal Time
Corrections.
0 0 - 9999999999 [Operation
/Count and RevData
/TimeSync
/SNTP]
NoOfBigSyncs Service counter: Total Number of big Time
Corrections.
0 0 - 9999999999 [Operation
/Count and RevData
/TimeSync
/SNTP]
NoOfFiltSyncs Service counter: Total Number of filtered Time
Corrections.
0 0 - 9999999999 [Operation
/Count and RevData
/TimeSync
/SNTP]
NoOfSlowTrans Service counter: Total Number of slow Transfers. 0 0 - 9999999999 [Operation
/Count and RevData
/TimeSync
/SNTP]