EDR-3000 IM02602003E
Device Planning Parameters of the IRIG-B00X
Parameter Description Options Default Menu path
Mode Mode Do not use,
Use
Use [Device Planning]
Direct Commands of the IRIG-B00X
Parameter Description Setting range Default Menu path
Res IRIG-B Cr Resetting of the Diagnosis Counters: IRIG-B Inactive,
Active
Inactive [Operation
/Reset]
Global Protection Parameters of the IRIG-B00X
Parameter Description Setting range Default Menu path
Function Permanent activation or deactivation of module/element. Inactive,
Active
Inactive [Device Para
/Time
/TimeSync
/IRIG-B]
IRIG-B00X Determination of the Type: IRIG-B00X. IRIG-B types
differ in types of included “Coded Expressions” (year,
control-functions, straight-binary-seconds).
IRIGB-000,
IRIGB-001,
IRIGB-002,
IRIGB-003,
IRIGB-004,
IRIGB-005,
IRIGB-006,
IRIGB-007
IRIGB-000 [Device Para
/Time
/TimeSync
/IRIG-B]
www.eaton.com 257