EDR-3000 IM02602003E
Direct Commands of the Modbus
®
Parameter Description Setting range Default Menu path
Res Diagn Cr All Modbus Diagnosis Counters will be reset. Inactive,
Active
Inactive [Operation
/Reset]
Global Protection Parameters of the Modbus
®
Parameter Description Setting range Default Menu path
Slave ID Device address (Slave ID) within the bus system. Each
device address has to be unique within a bus system.
Only available if:Device Planning = RTU
1 - 247 1 [Device Para
/Modbus]
Unit ID The Unit Identifier is used for routing. This parameter is
to be set, if a Modbus RTU and a Modbus TCP network
should be coupled.
Only available if:Device Planning = TCP
1 - 255 255 [Device Para
/Modbus]
TCP Port Config TCP Port Configuration. This parameter is to be set only
if the default Modubs TCP Port should not be used.
Only available if:Device Planning = TCP
Default,
Private
Default [Device Para
/Modbus]
Port Port number
Only available if:Device Planning = TCP And Only
available if: TCP Port Config = Private
502 - 65535 502 [Device Para
/Modbus]
t-timeout Within this time the answer has to be received by the
Communication system, otherwise the request will be
disregarded. In that case, the Communication system
detects a communication failure and the Communication
System has to send a new request.
Only available if:Device Planning = RTU
0.01 - 10.00s 1s [Device Para
/Modbus]
Baud rate Baud rate
Only available if:Device Planning = RTU
1200,
2400,
4800,
9600,
19200,
38400
19200 [Device Para
/Modbus]
www.eaton.com 271