EDR-3000 IM02602003E
Adaptive Parameter Set Activation Signals
Name Description
-.- No assignment
SOTF.enabled Signal: Switch Onto Fault enabled. This Signal can be used to modify Overcurrent Protection Settings.
CLPU.enabled Signal: Cold Load enabled
AR.Running Signal: Auto Reclosing Running
AR.Pre Shot Pre Shot Control
AR.Shot 1 Shot Control
AR.Shot 2 Shot Control
AR.Shot 3 Shot Control
AR.Shot 4 Shot Control
AR.Shot 5 Shot Control
AR.Shot 6 Shot Control
DI-4P X1.DI 1 Signal: Digital Input
DI-4P X1.DI 2 Signal: Digital Input
DI-4P X1.DI 3 Signal: Digital Input
DI-4P X1.DI 4 Signal: Digital Input
DI-8P X1.DI 1 Signal: Digital Input
DI-8P X1.DI 2 Signal: Digital Input
DI-8P X1.DI 3 Signal: Digital Input
DI-8P X1.DI 4 Signal: Digital Input
DI-8P X1.DI 5 Signal: Digital Input
DI-8P X1.DI 6 Signal: Digital Input
DI-8P X1.DI 7 Signal: Digital Input
DI-8P X1.DI 8 Signal: Digital Input
Logic.LE1.Gate Out Signal: Output of the logic gate
Logic.LE1.Timer Out Signal: Timer Output
Logic.LE1.Out Signal: Latched Output (Q)
Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE2.Gate Out Signal: Output of the logic gate
Logic.LE2.Timer Out Signal: Timer Output
Logic.LE2.Out Signal: Latched Output (Q)
Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)
Logic.LE3.Gate Out Signal: Output of the logic gate
Logic.LE3.Timer Out Signal: Timer Output
Logic.LE3.Out Signal: Latched Output (Q)
Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)
www.eaton.com 295