EDR-3000 IM02602003E
The housing must be carefully grounded. Connect a ground cable (4 to 6
mm
2
[AWG 12-10] / 1.7 Nm [15 In-lb]) to the housing, using the screw that is
marked with the ground symbol (at the rear side of the device).
The power supply card needs a separate ground connection (2.5 mm
2
[AWG 14] / 0.56-0.79 Nm [5-7 In-lb]) at terminal X1.
DO NOT over-tighten the mounting nuts of the relay
(0.164 X32 ). Check the torque by means of a torque wrench (1.7 Nm [15 In-
lb]). Over-tightening the mounting nuts could cause personal injury or damage
the relay.