EDR-3000 IM02602003E
Parameter Description Setting range Default Menu path
Count2 Open Counts Allowed #2
Only available if:Bwear Curve Fc = Active
1 - 32000 10000 [Control
/Bkr
/Bwear]
Current3 Interrupted Current Level #3
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA 1.15kA [Control
/Bkr
/Bwear]
Count3 Open Counts Allowed #3
Only available if:Bwear Curve Fc = Active
1 - 32000 10000 [Control
/Bkr
/Bwear]
Current4 Interrupted Current Level #4
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA 3.00kA [Control
/Bkr
/Bwear]
Count4 Open Counts Allowed #4
Only available if:Bwear Curve Fc = Active
1 - 32000 1900 [Control
/Bkr
/Bwear]
Current5 Interrupted Current Level #5
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA 5.00kA [Control
/Bkr
/Bwear]
Count5 Open Counts Allowed #5
Only available if:Bwear Curve Fc = Active
1 - 32000 850 [Control
/Bkr
/Bwear]
Current6 Interrupted Current Level #6
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA 6.00kA [Control
/Bkr
/Bwear]
Count6 Open Counts Allowed #6
Only available if:Bwear Curve Fc = Active
1 - 32000 500 [Control
/Bkr
/Bwear]
Current7 Interrupted Current Level #7
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA 13.00kA [Control
/Bkr
/Bwear]
Count7 Open Counts Allowed #7
Only available if:Bwear Curve Fc = Active
1 - 32000 110 [Control
/Bkr
/Bwear]
www.eaton.com 387