EDR-3000 IM02602003E
Parameter Description Setting range Default Menu path
ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/ZI
/General Settings]
Blo TripCmd Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
Inactive [Protection Para
/<1..4>
/ZI
/General Settings]
ExBlo TripCmd Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/ZI
/General Settings]
ZI OUT Fc Zone Interlocking Out activate (allow) / inactivate
(disallow)
Inactive,
Active
Active [Protection Para
/<1..4>
/ZI
/Zone Out]
Fault Type Fault Type Phase,
Ground,
Both
Both [Protection Para
/<1..4>
/ZI
/Zone Out]
Trip Signal: Zone Interlocking Trip Inactive,
Active
Active [Protection Para
/<1..4>
/ZI
/Zone Trip]
Fault Type Fault Type Phase,
Ground,
Both
Both [Protection Para
/<1..4>
/ZI
/Zone Trip]