EDR-3000 IM02602003E
Setting Group Parameters of the Current Unbalance Module
Parameter Description Setting range Default Menu path
Function Permanent activation or deactivation of module/element. Inactive,
Active
Inactive [Protection Para
/<1..4>
/Unbalance-Prot
/46[1]]
ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Unbalance-Prot
/46[1]]
Blo TripCmd Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Unbalance-Prot
/46[1]]
ExBlo TripCmd Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Unbalance-Prot
/46[1]]
Threshold The Threshold setting defines a minimum operating
current magnitude of I2 for the 46 function to operate,
which ensures that the relay has a solid basis for
initiating a current unbalance trip. This is a supervisory
function and not a trip level.
Only available if: Device Planning: 51Q.Mode = 46
0.01 - 4.00In 0.1In [Protection Para
/<1..4>
/Unbalance-Prot
/46[1]]
%(I2/I1) The %(I2/I1) setting is the unbalance trip pickup setting. It
is defined by the ratio of negative sequence current to
positive sequence current (% Unbalance=I2/I1). Phase
sequence will be taken into account automatically.
Only available if: %(I2/I1) = Use
2 - 40% 46[1]: 40%
46[2]: 20%
[Protection Para
/<1..4>
/Unbalance-Prot
/46[1]]
t Tripping delay
Only available if: Characteristic = DEFT
0.00 - 300.00s 46[1]: 10s
46[2]: 20s
[Protection Para
/<1..4>
/Unbalance-Prot
/46[1]]
www.eaton.com 479