EDR-3000 IM02602003E
Apply a balanced three-phase current system (nominal currents).
Switch off IA (the threshold value »
Threshold«
for »
I2 Fund.«
must be below 33%).
Measure the tripping time.
The present current unbalance »
I2 Fund.«
corresponds with 1/3 of the existing phase current displayed.