EDR-3000 IM02602003E
After the
»t load Off«
timer has expired, the signal ”CPLU.ENABLED “=1 has to become true.
Write down the measured time.
Successful test result:
The measured total tripping delays or individual tripping delays, threshold values, and drop-out ratios correspond with
those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Technical Data sec-
tion.