EDR-3000 IM02602003E
11
Ready
An activated autoreclose function is considered to be in »READY« state when all of the following conditions are true:
The breaker is in closed position;
The Manual-Close-Block-timer elapses after a breaker manual/remote close operation;
The autoreclose function is not initiated from any initiate (start) functions; and
No external or internal AR blocking signals are present.
13
Waiting Bkr Open
While in the »WAITING BKR OPEN« state, the autoreclosure supervises if the breaker is really tripped (open) after receiving
the trip flag of the initiate protection function within a pre-set breaker supervision time (200 ms). If this is the case, the
autoreclosure starts the programmed dead timer and goes to the dead timing state »
t-dead«
.
www.eaton.com 512