EDR-3000 IM02602003E
Global Protection Parameters of the Module Automatic Reclosure
Parameter Description Setting range Default Menu path
ExBlo1 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/AR
/General Settings]
ExBlo2 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/AR
/General Settings]
Ex Shot Inc The AR Shot counter will be incremented by this external
Signal. This can be used for Zone Coordination (of
upstream Auto Reclosure devices).
1..n, DI-LogicList -.- [Protection Para
/Global Prot Para
/AR
/General Settings]
Ex Lock The auto reclosure will locked out by this external Signal
(set into the lockout state).
1..n, DI-LogicList -.- [Protection Para
/Global Prot Para
/AR
/General Settings]
DI Reset Ex Lock The Lockout State of the AR can be reset by a digital
input.
1..n, DI-LogicList -.- [Protection Para
/Global Prot Para
/AR
/General Settings]
www.eaton.com 523