EDR-3000 IM02602003E
Automatic Reclosure Module Values
Value Description Default Size Menu path
AR Shot No. Counter - Auto Reclosure Attempts 0 0 - 6 [Operation
/Count and RevData
/AR]
Total number Cr Total number of all executed Automatic
Reclosures Attempts
0 0 - 65536 [Operation
/Count and RevData
/AR]
Cr successfl Total number of successfully executed Automatic
Reclosures
0 0 - 65536 [Operation
/Count and RevData
/AR]
Cr failed Total number of unsuccessfully executed
automatic reclosure attempts
0 0 - 65536 [Operation
/Count and RevData
/AR]
Cr Service Alarm1 Remaining numbers of ARs until Service Alarm 1 1000 0 - 1000 [Operation
/Count and RevData
/AR]
Cr Service Alarm2 Remaining numbers of ARs until Service Alarm 2 65536 0 - 65536 [Operation
/Count and RevData
/AR]
Max Shots / h Cr Counter for the maximum allowed shots per hour. 0 0 - 65536 [Operation
/Count and RevData
/AR]