EDR-3000 IM02602003E
Setting Group Parameters of the Trip Circuit Monitoring Module
Parameter Description Setting range Default Menu path
Function Permanent activation or deactivation of module/element. Inactive,
Active
Inactive [Protection Para
/<1..4>
/Supervision
/TCM]
ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Supervision
/TCM]
t-TCM Tripping delay time of the Trip Circuit Supervision 0.10 - 10.00s 0.2s [Protection Para
/<1..4>
/Supervision
/TCM]
www.eaton.com 581