EDR-3000 IM02602003E
States of the Inputs of the Wired Inputs Module
Name Description Assignment via
Bkr Trouble-I Breaker Trouble [Device Para
/Wired Inputs]
52a M1-I State of the module input: Main 1 Breaker Closed [Device Para
/Wired Inputs]
52b M1-I State of the module input: Main 1 Breaker Open [Device Para
/Wired Inputs]
TOCa M1-I State of the module input: Main 1 Breaker Connected [Device Para
/Wired Inputs]
43/10 M1-I State of the module input: Main 1 Breaker Selected To Trip [Device Para
/Wired Inputs]
52a M2-I State of the module input: Main 2 Breaker Closed [Device Para
/Wired Inputs]
52b M2-I State of the module input: Main 2 Breaker Open [Device Para
/Wired Inputs]
TOCa M2-I State of the module input: Main 2 Breaker Connected [Device Para
/Wired Inputs]
43/10 M2-I State of the module input: Main 2 Breaker Selected To Trip [Device Para
/Wired Inputs]
52a T-I State of the module input: Tie Breaker Closed [Device Para
/Wired Inputs]
52b T-I State of the module input: Tie Breaker Open [Device Para
/Wired Inputs]
TOCa T-I State of the module input: Tie Breaker Connected [Device Para
/Wired Inputs]
43/10 T-I State of the module input: Tie Breaker Selected To Trip [Device Para
/Wired Inputs]
43 M-I State of the module input: System In Manual [Device Para
/Wired Inputs]
43 A-I State of the module input: System in Auto [Device Para
/Wired Inputs]
43 P1-I State of the module input: Preferred Source 1 [Device Para
/Wired Inputs]
43 P2-I State of the module input: Preferred Source 2 [Device Para
/Wired Inputs]
www.eaton.com 74