Integratethemeterwiththecontrolsystem
Postrequisites
Important
WheneveryouchangeanmAoutputparameter,verifyallothermAoutputparametersbeforereturning
theowmetertoservice.Insomesituations,thetransmitterautomaticallyloadsasetofstoredvalues,
andthesevaluesmaynotbeappropriateforyourapplication.
7.1.1ConfiguremAOutputProcessVariable
Display
OFF-LINEMAINT→OFF-LINECONFG→IO→AO1→SRC
OFF-LINEMAINT→OFF-LINECONFG→IO→AO2→SRC
ProLinkII
ProLink→Conguration→AnalogOutput→Primary/SecondaryOutput→PV/SVIs
FieldCommunicatorCongure→ManualSetup→Inputs/Outputs→mAOutput1→PrimaryVariable
Congure→ManualSetup→Inputs/Outputs→mAOutput2→SecondaryVariable
mAOutputProcessVariablecontrolsthevariablethatisreportedoverthemAoutput.
Prerequisites
Ifyouplantocongureanoutputtoreportvolumeow,ensurethatyouhavesetVolumeFlowTypeas
desired:LiquidorGasStandardVolume.
Ifyouplantocongureanoutputtoreportaconcentrationmeasurementprocessvariable,ensurethat
theconcentrationmeasurementapplicationisconguredsothatthedesiredvariableisavailable.
IfyouareusingtheHARTvariables,beawarethatchangingthecongurationofmAOutputProcess
VariablewillchangethecongurationoftheHARTPrimaryVariable(PV)and/ortheHARTSecondary
Variable(SV).
Procedure
SetmAOutputProcessVariableasdesired.
Defaultsettingsareasfollows:
•PrimarymAoutput:MassFlowRate
•SecondarymAoutput:Density
OptionsformAOutputProcessVariable
ThetransmitterprovidesabasicsetofoptionsformAOutputProcessVariable,plusseveral
application-specicoptions.Differentcommunicationstoolsusedifferentlabelsfortheoptions.
OptionsformAOutputProcessVariablearelistedinT able7-1.
Table7-1OptionsformAOutputProcessVariable
Label
ProcessvariableDisplayProLinkIIFieldCommunicator
MassowrateMFLOW
MassFlowRate
Masso
VolumeowrateVFLOW
VolumeFlowRate
Volo
118
MicroMotion9739MVDTransmitters