Troubleshooting
Table10-2Statusalarmsandrecommendedactions
continued
AlarmcodeDescriptionCauseRecommendedactions
A113
SecondarymAoutput
saturated
•Checkprocessconditions.Actual
conditionsmaybeoutsideofthenormally
expectedconditionsforwhichtheoutput
iscongured.
•Verifyprocessconditions,checking
especiallyforairintheowtubes,tubes
notlled,foreignmaterialinthetubes,or
coatinginthetubes.
•Verifythatthemeasurementunitsare
conguredcorrectlyforyourapplication.
•Purgetheowtubes.
•CheckthesettingsofUpperRangeValueand
LowerRangeValue.SeeSection10.17.
A114
SecondarymAoutput
xed
•Checkthatthetransmitterisinlooptest
mode.
•ExitmAoutputtrim.
•Checkthattheoutputhasbeenxedvia
digitalcommunication.
A115ExternalinputerrorTheHARTpolling
connectiontoan
externaldevicehas
failed.Noresponse
receivedfrompolled
device.
ThemAinput
connectiontoan
externaldevicehas
failed.Noresponse
receivedfromthe
externaldevice.
•Verifytheexternaldeviceoperation.
•Verifythewiringbetweenthetransmitter
andtheexternaldevice.
•VerifytheHARTpollingconguration.
•VerifythemAinputconguration.
A116APItemperature
outsidestandardrange
•Verifyprocessconditions.
•Verifythecongurationofthepetroleum
measurementtabletypeandtemperature.
A117
APIdensityoutof
limits
•Verifyprocessconditions.
•Verifythecongurationofthepetroleum
measurementtabletypeanddensity.
A118
Discreteoutput1xedTheuserhasxedthe
discreteoutput.
•Checkthatthetransmitterisinlooptest
mode.
A120
Concentration
measurement:unable
toxcurvedata
•Verifythecongurationofthe
concentrationmeasurementapplication.
ConfigurationandUseManual