Proline t-mass I 300 HART Diagnostics and troubleshooting
Endress+Hauser 147
Diagnostic
number
Short text Remedy instructions Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
Diagnostic of configuration
330 Flash file invalid 1. Update firmware of device
2. Restart device
M Warning
331 Firmware update failed 1. Update firmware of device
2. Restart device
F Warning
410 Data transfer 1. Check connection
2. Retry data transfer
F Alarm
412 Processing download Download active, please wait C Warning
431 Trim 1 to n Carry out trim C Warning
437 Configuration
incompatible
Restart device F Alarm
438 Dataset 1. Check data set file
2. Check device configuration
3. Up- and download new
configuration
M Warning
441 Current output 1 to n 1. Check process
2. Check current output settings
S Warning
1)
442 Frequency output 1 to n 1. Check process
2. Check frequency output settings
S Warning
1)
443 Pulse output 1 to n 1. Check process
2. Check pulse output settings
S Warning
1)
444 Current input 1 to n 1. Check process
2. Check current input settings
S Warning
1)
453 Flow override Deactivate flow override C Warning
484 Failure mode simulation Deactivate simulation C Alarm
485 Measured variable
simulation
Deactivate simulation C Warning
486 Current input 1 to n
simulation
Deactivate simulation C Warning
491 Current output 1 to n
simulation
Deactivate simulation C Warning
492 Simulation frequency
output 1 to n
Deactivate simulation frequency
output
C Warning
493 Simulation pulse output
1 to n
Deactivate simulation pulse output C Warning
494 Switch output simulation
1 to n
Deactivate simulation switch output C Warning
495 Diagnostic event
simulation
Deactivate simulation C Warning
496 Status input simulation Deactivate simulation status input C Warning
520 I/O 1 to n hardware
configuration invalid
1. Check I/O hardware
configuration
2. Replace wrong I/O module
3. Plug the module of double pulse
output on correct slot
F Alarm
537 Configuration 1. Check IP addresses in network
2. Change IP address
F Warning
539 Flow computer
configuration incorrect
1. Check input value (pressure,
temperature)
2. Check allowed values of the
medium properties
S Alarm