Proline t-mass I 300 HART Commissioning
Endress+Hauser 99
Parameter overview with brief description
Parameter Prerequisite Description User interface / 
Selection / User
entry
Factory setting
Terminal number Shows the terminal numbers
used by the relay output
module.
Not used
24-25 (I/O 2)
22-23 (I/O 3)
Relay output function Select the function for the
relay output.
Closed
Open
Diagnostic
behavior
Limit
Flow direction
check
Digital Output
Assign limit The Limit option is selected in
the Relay output function
parameter.
Select process variable for limit
function.
Temperature
Mass flow
Corrected volume
flow
FAD volume flow
*
Volume flow
Energy flow
*
Heat flow
*
Density
Flow velocity
2nd temperature
delta heat
*
Electronic
temperature
Totalizer 1
Totalizer 2
Totalizer 3
Assign diagnostic behavior In the Relay output function
parameter, the Diagnostic
behavior option is selected.
Select diagnostic behavior for
switch output.
Alarm
Alarm or warning
Warning
Assign status In the Relay output function
parameter, the Digital Output
option is selected.
Select device status for switch
output.
Off
Low flow cut off
Switch-off value In the Relay output function
parameter, the Limit option is
selected.
Enter measured value for the
switch-off point.
Signed floating-point
number
Switch-off delay In the Relay output function
parameter, the Limit option is
selected.
Define delay for the switch-off
of status output.
0.0 to 100.0 s
Switch-on value The Limit option is selected in
the Relay output function
parameter.
Enter measured value for the
switch-on point.
Signed floating-point
number
Depends on country
and nominal
diameter
Switch-on delay In the Relay output function
parameter, the Limit option is
selected.
Define delay for the switch-on
of status output.
0.0 to 100.0 s
Failure mode Define output behavior in
alarm condition.
Actual status
Open
Closed
* Visibility depends on order options or device settings
9.4.12 Configuring the local display
The Display wizard guides you systematically through all the parameters that can
configured for configuring the local display.