Installation Proline t-mass I 300 HART
32 Endress+Hauser
5.3 Post-installation check
Is the device undamaged (visual inspection)?
Does the measuring device conform to the measuring point specifications?
For example:
Process temperature →  180
Process pressure (refer to the "Pressure-temperature ratings" section of the "Technical
Information" document)
Ambient temperature →  25
Measuring range →  164
Has the correct orientation been selected for the sensor →  19?
According to sensor type
According to medium properties
According to medium temperature
According to process pressure
Does the arrow on the sensor match the actual direction of flow of the medium through the
piping ?
Have sufficient inlet and outlet runs been provided upstream and downstream of the measuring
point →  21?
Correct sensor insertion depth?
Is the device adequately protected from precipitation and direct sunlight?
Is the device protected against overheating?
Is the device protected against excessive vibrations?
Gas property checked (e.g. purity, dryness, cleanness)?
Are the measuring point identification and labeling correct (visual inspection)?
Are the securing screw and securing clamp tightened securely?