System integration Proline t-mass I 300 HART
74 Endress+Hauser
Assignment Device variables
5 Temperature
6 Totalizer 1
7 Totalizer 2
8 Totalizer 3
8.3 Other settings
Burst mode functionality in accordance with HART 7 Specification:
Navigation
"Expert" menu → Communication → HART output → Burst configuration → Burst
configuration 1 to n
Burst configuration
Burst configuration 1 to n
Parameter overview with brief description
Parameter Description Selection / User entry
Burst mode 1 to n Activate the HART burst mode for burst message X. Off
On
Burst command 1 to n Select the HART command that is sent to the HART master. Command 1
Command 2
Command 3
Command 9
Command 33
Command 48
Burst variable 0 For HART command 9 and 33: select the HART device variable
or the process variable.
Mass flow
Corrected volume flow
FAD volume flow
*
Volume flow
Temperature
Density
Flow velocity
Pressure
Energy flow
*
Heat flow
*
2nd temperature delta heat
*
Electronic temperature
Totalizer 1
Totalizer 2
Totalizer 3
Percent of range
Measured current
Current input 1
*
Current input 2
*
Current input 3
*
Primary variable (PV)
Secondary variable (SV)
Tertiary variable (TV)
Quaternary variable (QV)
HART input
Not used
Burst variable 1 For HART command 9 and 33: select the HART device variable
or the process variable.
See the Burst variable 0 parameter.