Commissioning Proline t-mass I 300 HART
84 Endress+Hauser
Duct height
→  84
Duct width
→  84
Parameter overview with brief description
Parameter Prerequisite Description Selection / User entry
Installation direction Set sign of flow direction to match the
direction of the arrow on the sensor.
Flow in arrow direction
Flow against arrow
direction
Installation factor Enter factor to compensate the
mounting-related measurement error.
0.01 to 100.0
Pipe shape Only available with t-mass I. Select the shape of the pipe. Circular
Rectangular
Pipe inner diameter Only available with t-mass I. Enter the internal diameter of a circular
pipe.
0.050 to 5 m
Duct height Only available with t-mass I. Enter inner duct height. Duct height
and sensor shaft are parallel.
0.050 to 5 m
Duct width Only available with t-mass I. Enter inner duct width. The duct width
is vertical to the sensor shaft.
0.050 to 5 m
9.4.5 Configuring the status input
The Status input submenu guides the user systematically through all the parameters that
have to be set for configuring the status input.
Navigation
"Setup" menu → Status input
Status input 1 to n
Assign status input
→  85
Terminal number
→  85
Active level
→  85
Terminal number
→  85
Response time status input
→  85
Terminal number
→  85