Proline t-mass I 300 HART Installation
Endress+Hauser 25
P
2 ... 5 x DN
A0039447
 13 Installation of a pressure measuring point (P = pressure transmitter)
Installation conditions for nipples
Suitable support brackets must be used if installing in rectangular air ducts (or pipes
with thin walls).
90° (± 3°)
90° (± 3°)
D
Di
A0040684
D Ø 31.0 ± 0.5 mm (1.22 ± 0.019 in)
Di Ø 23.0 ± 0.5 mm (0.91 ± 0.019 in)
5.1.2 Environment and process requirements
Ambient temperature range
Measuring device –40 to +60 °C (–40 to +140 °F)
Order code for "Test, certificate", option JP:
–50 to +60 °C (–58 to +140 °F)
Readability of the local
display
–20 to +60 °C (–4 to +140 °F)
The readability of the display may be impaired at temperatures outside the
temperature range.
NOTICE
Danger of overheating
Ensure that the temperature at the lower end of the transmitter housing does not
exceed 80 °C (176 °F).
Ensure that sufficient convection takes place at the transmitter neck.
When using in potentially explosive atmospheres, observe the information in the
device-specific Ex documentation. For detailed information on the temperature tables,
see the separate document entitled "Safety Instructions" (XA) for the device.
Ensure that a sufficiently large area of the transmitter neck remains exposed. The
uncovered part serves as a radiator and protects the electronics from overheating and
excessive cooling.
If operating outdoors:
Avoid direct sunlight, particularly in warm climatic regions.
You can order a weather protection cover from Endress+Hauser→  159.