Electrical connection Proline t-mass I 300 HART
34 Endress+Hauser
Current input 0/4 to 20 mA
Standard installation cable is sufficient.
Status input
Standard installation cable is sufficient.
Cable diameter
Cable glands supplied:
M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in)
Spring-loaded terminals: Suitable for strands and strands with ferrules.
Conductor cross-section 0.2 to 2.5 mm
2
(24 to 12 AWG).
Requirements for the connecting cable – Remote display and operating module
DKX001
Optionally available connecting cable
A cable is supplied depending on the order option
Order code for measuring device: order code 030 for "Display; operation", option O
or
Order code for measuring device: order code 030 for "Display; operation", option M
and
Order code for DKX001: order code 040 for "Cable", option A, B, D, E
Standard cable
2 × 2 × 0.34 mm
2
(22 AWG) PVC cable with common shield (2 pairs, pair-
stranded)
Flame resistance According to DIN EN 60332-1-2
Oil-resistance According to DIN EN 60811-2-1
Shielding Tin-plated copper-braid, optical cover ≥ 85 %
Capacitance: core/shield ≤200 pF/m
L/R ≤24 µH/Ω
Available cable length 5 m (15 ft)/10 m (35 ft)/20 m (65 ft)/30 m (100 ft)
Operating temperature When mounted in a fixed position: –50 to +105 °C (–58 to +221 °F); when cable
can move freely: –25 to +105 °C (–13 to +221 °F)
Standard cable - customer-specific cable
No cable is supplied, and it must be provided by the customer (up to max.
300 m (1 000 ft)) for the following order option:
Order code for DKX001: Order code 040 for "Cable", option 1 "None, provided by customer,
max 300 m"
A standard cable can be used as the connecting cable.
Standard cable 4 cores (2 pairs); pair-stranded with common shield
Shielding Tin-plated copper-braid, optical cover ≥ 85 %
Capacitance: core/shield Maximum 1 000 nF for Zone 1, Class I, Division 1
L/R Maximum 24 µH/Ω for Zone 1, Class I, Division 1
Cable length Maximum 300 m (1 000 ft), see the following table