Device Functions Proline Promass 83 MODBUS RS485 3 Block MEASURED VARIABLES
Endress+Hauser 17
UNIT CORRECTED
VOLUME FLOW
MODBUS register:
Data type:
Access:
0404
2105
Integer
read/write
For selecting the unit for displaying the corrected volume flow (corrected
volume/time).
The unit you select here is also valid for:
• Current output
• Frequency output
• Relay switch points (limit value for corrected volume flow, flow direction)
• Low flow cut off
Options:
Metric:
0 = Nl/s
1 = Nl/min
2 = Nl/h
3 = Nl/day
4 = Nm
3
/s
5 = Nm
3
/min
6 = Nm
3
/h
7 = Nm
3
/day
US:
8 = Sm
3
/s
9 = Sm
3
/min
10 = Sm
3
/h
11 = Sm
3
/day
12 = Scf/s
13 = Scf/min
14 = Scf/h
15 = Scf/day
Factory setting: Nm
3
/h
UNIT CORRECTED
VOLUME
MODBUS register:
Data type:
Access:
0405
2106
Integer
read/write
For selecting the unit for displaying the corrected volume.
The unit you select here is also valid for:
• Pulse value (e.g. Nm
3
/p)
Options:
Metric:
0 = Nm
3
1 = Nl
US:
2 = Sm
3
3 = Scf
Factory setting: Nm
3
! Note!
The unit of the totalizers is independent of your choice here. The unit for each
totalizer is selected separately for the totalizer in question.
Function description
MEASURED VARIABLES → SYSTEM UNITS → CONFIGURATION