Pool Installation / Commissioning
WT.050.570.000.DE.IM.0714 133
2.7
No. Step Reference Compl.
54 Check the setting of the "Floccula-
tion" flocculation control, adjust if
necessary
2.6.4 and 1.3.3
(Display 1.7.7
and 1.7.8)
55 Check the setting of the DIN con-
tact "DIN 19643 funct.", adjust if
necessary
2.6.4 and 1.3.3
(Display 1.7.7.)
56 With the "Dosing rate MANUAL"
menu check all connected dosing
equipment for correct function
1.3.3
(Display 3.1)
57 After approximately one hour run-
ning-in time calibrate the fitted
sensors
1.3.4
58 Set to the "AUTO" operating mode 1.3.3
(Menu 3)
59 After 24 hours running time repeat
calibration
1.3.4