132 WT.050.570.000.DE.IM.0714
Installation / Commissioning DEPOLOX
®
Pool
2.7
No. Step Reference Compl.
If conductivity measurement is
available:
42 Set control outputs for conductivi-
ty, if necessary set "Pulses max./
min"
1.3.3
(Display 1.5.1)
43 Set the control direction 1.3.3
(Display 1.5.1)
44 Check setpoint for conductivity
control, adjust if necessary
1.3.3
(Display 1.5.2)
45 Adapt the value for "Xp" to the
control loop, if necessary optimi-
se in small steps
1.3.3
(Display 1.5.2)
46 If a dosing pump is used, check
the "Tp" parameter, if necessary
adapt to pump
1.3.3
(Display 1.5.2)
47 Check limit values for conductivity
("Min" and "Max"), adjust if neces-
sary
1.3.3
(Display 1.5.3)
48 Check measuring range for con-
ductivity, adjust if necessary
1.3.3
(Display 1.5.4)
Subsequent procedures:
49 Configure the alarms as required 2.6.2 and 1.3.3
(Display 1.7.1 to
1.7.3)
50 Configure the analog outputs as
required
1.3.3
(Display 1.7.4)
51 Set "DI (2)" and "DI (3)" as re-
quired
1.3.3
(Display 1.7.5)
52 Configure the printer interface
"RS232"
2.6.5 and 1.3.3
(Display 1.7.6.)
53 Configure the RS485 interface as
required
2.6.5 and 1.3.3
(Display 1.7.6.)