EasyManua.ls Logo

Evoqua DEPOLOX - Page 45

Evoqua DEPOLOX
178 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DEPOLOX
®
Pool Operation
WT.050.570.000.DE.IM.0714 45
1.3
Cl
2
settings
(menu 1.1)
Basic display Refer to main menu
Menu select Display of all available menus
Menu Cl
2
Display of all available Cl
2
settings
Cl
2
actuator Control output
Ty 10 s ... 180 s
Tp 010 ... 180 s
Ym Calibration Auto / -
Ym Calibration 0/100 % manual calibration
max. Pulses /min100 / 120
Cl
2
parameters Setpoint 0.10 mg/l ... End of measuring range
Xp 0001 ... 1000 %
Tn 000.0 ... 100.0 min
Ymin, Ymax 000.0 ... 100.0 %
Hysteresis 0.01 ... 0.5 mg/l
min ON for dosing contact 1...59 min.
Cl
2
parameters ECO Setpoint
ECO
0.10 mg/l ... End of measuring range
Xp
ECO
0001 ... 1000 %
Tn
ECO
000.0 ... 100.0 min
Circul.
ECO
ON limit value for switching to ECO mode
for dynamic circulation reduction, 0 ... 100%
Cl
2
limit values Min / Max setpoint min / max setpoint for cedox mode
MIN / Max 0.00 mg/l ... End of measuring range
Hysteresis 0.01 ... 0.25 mg/l or 0.1 ... 2.5 mg/l
Cl
2
measuring range Measuring range0 ... 1 mg/l to 0 ... 20 mg/l
Upot 0 ... 1000 mV (chlorine measuring cell)
µA range 0 µA, 100 µA, 200 µA, 1000 µA
Cl
2
adaption Tu dead time, 1 ... 3600 s
Ts rise time, 0.1 ... 480.0 min
Tu
ECO
during ECO mode, 1 ... 3600 s
Ts
ECO
during ECO mode, 0.1 ... 480.0 min
Circulation
circulation, during which Tu and TS are evaluated
Circul.
ECO
On
circulation, during which Tu
ECO
and TS
ECO
are eval.
ADAPT Start adaption or check last adaption
Cl
2
Peak chlorination Time max. 5 times per week
Interval weekly, every 2, 3, 4 weeks
Cl2 value chlorine value during peak chlorination, 0...10/20 mg/l
Duration duration of the peak chlorination, 0...10 h
Max delay max. time until the peak chlorine value is reached
alarm/Cl-N Dos alarms and Cl-N controller switched on/off
during peak chlorination
Electr.Pos.w.Ym
Dosing pump 2P
Analog output.2P
Electr.Pos.wo.Ym
Pulse pump 2P
Dosing contact for Cl2 dosing with hysteresis and
min swith-on time (e.g. for OSEC-A)

Table of Contents

Related product manuals