EasyManua.ls Logo

Evoqua DEPOLOX - Page 60

Evoqua DEPOLOX
178 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
60 WT.050.570.000.DE.IM.0714
Operation DEPOLOX
®
Pool
1.3
Analog out mA 1 ... 4 
mA signal 0 ... 20 mA / 4 ... 20 mA
NOTE
mA 1: Not available when Cl
2
control output set to "analog output"
(Display 1.1.1)
mA 2: Not available when pH control output on "analog output"
(Display 1.2.1)
mA 3: Not available when conductivity control output on "analog
output"
(Display 1.5.1)
Digital input
DI (2) / DI (3) Each digital output can be assigned a
parameter with the softkey "SELECT"
CONTROLLER STOP Yout = 0 %, positioner closed, pumps off,
mA analog output = 0 %
CONTROLLER CONST Yout remains constant, i.e. the control
signals are kept constant
MA CONSTANT All mA outputs remain unchanged.
CHANGEOVER MODE When DI is activated, changeover from
Automatic to Manual, positioner constant,
pump off, mA analog output= 0 %
ECONOMIC When DI is activated, the ECO
parameters are used for chlorine and
flocculation
control
Interface
RS232 
RS485 address Bus addresses 00 ... 31
CAN segment Segment address of the CAN bus, 0...63
External functions
(Release external
control functions)
Flocculation Off / On
DIN 19643 funct. Release contact when DIN values
are met, e.g. for decreasing circulation
Off / On)
Cl
2
pH
mV
Cl-N
Conductivity
°C
Ym / Yout Cl
2
Off
Printer
IAP-Download
Off

Table of Contents

Related product manuals