5. Parameter
5−10
Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH
5.2.4 Enable and stop with parametrisation
The parametrisation in the cyclical I/O data requires that the
CCON.STOP signal is not set, since operation enable is not
possible.
Commissioning parameters require that the controller is
locked when writing.
Transferring parameters has the following effects on the
CCON.ENABLE and CCON.STOP signals
Operating mode
Read: CCON Write: CCON
.ENABLE .STOP .ENABLE .STOP
Record selection x x x x
Direct mode x x x x
Commissioning x x 0 x
Parametrisation x 0 0 / x
1)
x / 0
1)
1)
With commissioning parameters CCON.ENABLE = 0 must be set
Tab.5/6: Effect of the parameter transfer to CCON