A. Notes on commissioning and service
A−16
Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH
Example:
With a DBCI−25−500 the effective length of 501.63 mm is
read when commissioning with hardware and copied
to the setpoint configuration. Without hardware a value
of 500.00 mm must be programmed.
When ultimately connecting the hardware, the user can
adopt the effective length. This does not occur automati
cally. If the projected
nominal and effective length is not
adjusted, the CMAX accepts a variation of 5.00 mm between
the projected length and the nominal length stored in the
drive without issuing an error or warning.
Serial numbers and
sampling time
The serial numbers of the sensor and valve and the
sampling time of the sensor
(measuring system) are also
not known when commissioning offline. This data is auto
matically adopted after connecting the hardware, if the
remaining data complies with the connected components.