QUANTUM™ LX EVAPORATOR CONTROL PANEL
OPERATION
090.610-O (MAR 2016)
Page 45
• Minimum – The minimum speed for the
variable speed fan output.
• Cycling – When enabled, the fans will con-
tinue to switch on periodically when the
heating requirement is satised.
Transition – When a mode has both heating and cool-
ing enabled, it is important to specify the transition tem-
perature to limit delays associated with the Pre-heat and
Post-heat stages. This allows for the Pre-heat stages to
start before the temperature falls below the Hot Gas On
setpoint. Similarly, as the temperature is rising toward the
Cooling On setpoint, the Post-heat stages can begin be-
fore cooling is required.
• Cooling To Heating – When the temperature
falls below this value, Pre-heat stages will be
executed.
• Heating To Cooling – When the temperature
exceeds this value, the Post-heat stages will be
executed.