3.4 Programming Mode
3-41
Chapter 3
KEYPAD FUNCTIONS
Table 3.4-14 Alarm Information Displayed
LED monitor
(item No.)
Item Description
6_00
Output frequency Output frequency before slip compensation
6_01
Output current Output current
6_02
Output voltage Output voltage
6_03
Calculated torque Calculated torque
6_04
Reference frequency Reference frequency
6_05
Rotational direction
Rotational direction being outputted
f
: forward,
r
: reverse, ----: stop
6_06
Running status
Running status is displayed in 4-digit hexadecimal format. Refer to
"Displaying running status (
3_07
) and running status 2 (
3_23
)" in
Section 3.4.4 "Monitoring the running status."
6_07
Cumulative run time
Shows the content of the cumulative power-ON time counter of the
inverter.
Counter range: 0 to 65,535 hours
Display: Upper 2 digits and lower 3 digits are displayed alternately.
Example:
0
⇔
535h
(535 hours)
65
⇔
535h
(65,535 hours)
The lower 3 digits are displayed with
h
(hour) at the
least significant digit.
When the count exceeds 65,535, the counter will be reset to "0" and start
over again.
6_08
Startup count for motor
Shows the content of the startup counter for the motor selected (i.e., the
number of run commands issued).
Counter range: 0 to 65,530 times
Display range:
0
to
9999
If the count exceeds 10,000, the x10 LED turns ON and
the LED monitor shows one-tenth of the value.
When the count exceeds 65,530, the counter will be reset to "0" and start
over again.
6_09
DC link bus voltage
Shows the DC link bus voltage of the inverter main circuit.
Unit: V (volts)
6_10
Temperature inside the
inverter
Shows the temperature inside the inverter.
Unit: °C
6_11
Max. temperature of
heat sink
Shows the temperature of the heat sink.
Unit: °C
6_12
Terminal I/O signal
status
(displayed with the
ON/OFF of LED
segments)
6_13
Terminal input signal
status
(in hexadecimal)
6_14
Terminal output signal
status
(in hexadecimal)
Displays the ON/OFF state of the digital I/O terminals. Refer to
"Displaying control I/O signal terminals"
in Section 3.4.5 "Checking I/O
signal status" for details.