5.2 Function Code Tables
5-7
Function
Code Tables
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
Chapter 5 Function Code
Table 5.2-6
E codes: Extension Terminal Functions
Drive control
Code Name Data setting range
Change
when
running
Data
copying
Default
setting
V/f
PG
V/f
w/o
PG
w/
PG
To rq ue
control
Refer to
page:
E01 Terminal [X1] Function 0 (1000): Select multi-frequency (0 to 1 step) (SS1) N Y 0 Y Y Y Y N 5-122
E02 Terminal [X2] Function 1 (1001): Select multi-frequency (0 to 3 steps) (SS2) N Y 1 Y Y Y Y N
E03 Terminal [X3] Function 2 (1002): Select multi-frequency (0 to 7 steps) (SS4) N Y 2 Y Y Y Y N
E04 Terminal [X4] Function 3 (1003): Select multi-frequency (0 to 15 steps) (SS8) N Y 3 Y Y Y Y N
E05 Terminal [X5] Function 4 (1004): Select ACC/DEC time (2 steps) (RT1) N Y 4 Y Y Y Y N
E06 Terminal [X6] Function 5 (1005): Select ACC/DEC time (4 steps) (RT2) N Y 5 Y Y Y Y N
E07 Terminal [X7] Function 6 (1006): Self-hold (HLD) N Y 6 Y Y Y Y Y
E08 Terminal [X8] Function 7 (1007): Coast to a stop (BX) N Y 7 Y Y Y Y Y
E09 Terminal [X9] Function 8 (1008): Reset alarm (RST) N Y 8 Y Y Y Y Y
9 (1009): Enable external alarm trip (THR)
(9 = Active OFF, 1009 = Active ON)
Y Y Y Y Y
10 (1010): Ready for jogging (JOG) Y Y Y Y N
11 (1011): Select frequency command 2/1 (Hz2/Hz1) Y Y Y Y N
12 (1012): Select motor 2 (M2) Y Y Y Y Y
13: Enable DC braking (DCBRK) Y Y Y Y N
14 (1014): Select torque limiter level 2/1 (TL2/TL1) Y Y Y Y Y
15: Switch to commercial power (50 Hz) (SW50) Y Y N N N
16: Switch to commercial power (60 Hz) (SW60) Y Y N N N
17 (1017): UP (Increase output frequency) (UP) Y Y Y Y N
18 (1018): DOWN (Decrease output frequency) (DOWN) Y Y Y Y N
19 (1019): Enable data change with keypad (data can be modified)
(WE-KP)
Y Y Y Y Y
20 (1020): Cancel PID control (Hz/PID) Y Y Y Y N
21 (1021): Switch normal/inverse operation (IVS) Y Y Y Y N
22 (1022): Interlock (IL) Y Y Y Y Y
23 (1023): Cancel torque control (Hz/TRQ) N N N N Y
24 (1024): Enable communications link via RS-485 or fieldbus (optional)
(LE)
Y Y Y Y Y
25 (1025): Universal DI (U-DI) Y Y Y Y Y
26 (1026): Enable auto search for idling motor speed at starting (STM) Y Y Y N Y
30 (1030): Force to stop (STOP)
(30 = Active OFF, 1030 = Active ON)
Y Y Y Y Y
32 (1032): Pre-excitation (EXITE) N N Y Y N
33 (1033): Reset PID integral and differential components (PID-RST) Y Y Y Y N
34 (1034): Hold PID integral component (PID-HLD) Y Y Y Y N
35 (1035): Select local (keypad) operation (LOC) Y Y Y Y Y
36 (1036): Select motor 3 (M3) Y Y Y Y Y
37 (1037): Select motor 4 (M4) Y Y Y Y Y
39: Protect motor from dew condensation (DWP) Y Y Y Y Y
40: Enable integrated sequence to switch to commercial power
(50 Hz) (ISW50)
Y Y N N N
41: Enable integrated sequence to switch to commercial power
(60 Hz) (ISW60)
Y Y N N N
47 (1047): Servo-lock command (LOCK) N N N Y N
48: Pulse train input (available only on terminal [X7] (E07)) (PIN) Y Y Y Y Y
49 (1049): Pulse train sign (SIGN)
(available on terminals except [X7] (E01 to E06, E08 and E09))
Y Y Y Y Y
59 (1059): Enable battery-driven operation (BATRY) Y Y Y Y Y
70 (1070): Cancel constant peripheral speed control (Hz/LSC) Y Y Y Y N
71 (1071): Hold the constant peripheral speed control frequency in the
memory (LSC-HLD)
Y Y Y Y N
72 (1072): Count the run time of commercial power-driven motor 1
(CRUN-M1)
Y Y N N Y
73 (1073): Count the run time of commercial power-driven motor 2
(CRUN-M2)
Y Y N N Y
74 (1074): Count the run time of commercial power-driven motor 3
(CRUN-M3)
Y Y N N Y
75 (1075): Count the run time of commercial power-driven motor 4
(CRUN-M4)
Y Y N N Y
76 (1076): Select droop control (DROOP) Y Y Y Y N
77 (1077): Cancel PG alarm (PG-CCL) N Y N Y Y
80 (1080): Cancel customizable logic (CLC) Y Y Y Y Y
81 (1081): Clear all customizable logic timers (CLTC) Y Y Y Y Y
100: No function assigned (NONE) Y Y Y Y Y
110 (1110): Servo-lock (Gain) (SLG2) N N N Y N
111 (1111): Force to stop (terminal block only) (STOP-T)
(111 = Active OFF, 1111 = Active ON)
Y Y Y Y Y
* Setting the value in parentheses ( ) shown above assigns a negative
logic output to a terminal. (True if OFF.)
E 10
A
cceleration Time 2 Y Y *1 Y Y Y Y N 5-76
E 11 Deceleration Time 2 Y Y *1 Y Y Y Y N 5-140
E 12
A
cceleration Time 3 Y Y *1 Y Y Y Y N
E 13 Deceleration Time 3 Y Y *1 Y Y Y Y N
E 14
A
cceleration Time 4 Y Y *1 Y Y Y Y N
E 15 Deceleration Time 4
0.00 to 6000 s
* Entering 0.00 cancels the acceleration time, requiring external
soft-start and -stop.
Y Y *1 Y Y Y Y N
*1 6.00 s for inverters with a capacity of 22 kW or below; 20.00 s for those with 30 kW or above