5.2 Function Code Tables
5-13
Function
Code Tables
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
Chapter 5 Function Code
Drive control
Code Name Data setting range
Change
when
running
Data
copying
Default
setting
V/f
PG
V/f
w/o
PG
w/
PG
To rq ue
control
Refer to
page:
H09 Starting Mode (Auto search) 0: Disable
1: Enable (Only at restart after momentary power failure)
2: Enable (At normal start and at restart after momentary power
failure)
N Y 0 Y Y N N N 5-184
H11 Deceleration Mode 0: Normal deceleration, 1: Coast-to-stop Y Y 0 Y Y Y Y N 5-186
H12 Instantaneous Overcurrent Limiting
(Mode selection)
0: Disable; 1: Enable Y Y 1 Y Y N N N 5-118
5-186
H13 Restart Mode after Momentary
Power Failure (Restart time)
0.1 to 10.0 s (ROM version earlier than 2000)
0.1 to 20.0 s (ROM version 2000 or later)
Y Y1, Y2 *2 Y Y Y Y N 5-83
H14 (Frequency fall rate) 0.00: Deceleration time selected by F08, 0.01 to 100.00 Hz/s, 999:
Follow the current limit command
Y Y 999 Y Y Y N N
5-186
H15 (Continuous running level) 200 to 300 V: (200 V class series)
400 to 600 V: (400 V class series)
Y Y2 235
470
Y Y N N N
H16 (Allowable momentary power failure
time)
0.0 to 30.0 s 999: Automatically determined by inverter Y Y 999 Y Y Y Y N
H18 Torque Control (Mode selection) 0: Disable (Speed control)
2: Enable (Torque current command)
3: Enable (Torque command)
N Y 0 N N Y Y Y
5-187
H26 Thermistor (for motor)
(Mode selection)
0: Disable
1: PTC (The inverter immediately trips with
0h4
displayed.)
2: PTC (The inverter issues output signal THM and continues to run.)
3: NTC (When connected)
Y Y 0 Y Y Y Y Y
5-189
H27 (Operation level) 0.00 to 5.00 V Y Y 0.35 Y Y Y Y Y
H28 Droop control -60.0 to 0.0 Hz Y Y 0.0 Y Y Y Y N 5-190
H30 Link Function
(Mode selection)
0:
1:
2:
3:
4:
5:
6:
7:
8:
Frequency command
F01/C30
RS-485 (Port 1)
F01/C30
RS-485 (Port 1)
RS-485 (Port 2)
RS-485 (Port 2)
F01/C30
RS-485 (Port 1)
RS-485 (Port 2)
Run command
F02
F02
RS-485 (Port 1)
RS-485 (Port 1)
F02
RS-485 (Port 1)
RS-485 (Port 2)
RS-485 (Port 2)
RS-485 (Port 2)
Y Y 0 Y Y Y Y Y
5-191
H42 Capacitance of DC link bus capacitor Indication for replacement (0000 to FFFF (hex.)) Y N - Y Y Y Y Y 5-193
H43 Cumulative run time of cooling fan Indication for replacement of cooling fan
Cumulative run time of cooling fan (in units of 10 hours)
Y N - Y Y Y Y Y
H44 Startup Counter for Motor 1 Indication for replacement (0000 to FFFF (hex.)) Y N - Y Y Y Y Y 5-196
H45 Mock alarm 0: Disable
1: Mock alarm is issued.
Y N 0 Y Y Y Y Y 5-197
5-198
H46 Starting Mode (Auto search delay
time 2)
0.1 to 10.0 s (ROM version earlier than 2000)
0.1 to 20.0 s (ROM version 2000 or later)
Y Y1, Y2 *6 Y Y Y N Y 5-184
5-197
H47 Initial capacitance of DC link bus
capacitor
Indication for replacement (0000 to FFFF (hex.)) Y N - Y Y Y Y Y 5-193
H48 Cumulative Run Time of Capacitors
on Printed Circuit Boards
Indication for replacement of capacitors
(The cumulative run time can be modified or reset in units of 10 hours.)
Y N - Y Y Y Y Y
5-197
H49 Starting Mode (Auto search delay
time 1)
0.0 to 10.0 s Y Y 0.0 Y Y Y Y Y 5-184
5-197
H50 Non-linear V/f Pattern 1 (Frequency) 0.0 (Cancel), 0.1 to 500.0 Hz N Y *7 Y Y N N N 5-72
H51 (Voltage) 0 to 240 V: Output an AVR-controlled voltage (for 200 V class series)
0 to 500 V: Output an AVR-controlled voltage (for 400 V class series)
N Y2 *8 Y Y N N N
5-197
H52 Non-linear V/f Pattern 2 (Frequency) 0.0 (Cancel), 0.1 to 500.0 Hz N Y 0.0 Y Y N N N
H53 (Voltage) 0 to 240 V: Output an AVR-controlled voltage (for 200 V class series)
0 to 500 V: Output an AVR-controlled voltage (for 400 V class series)
N Y2 0 Y Y N N N
H54 Acceleration Time (Jogging) 0.00 to 6000 s Y Y *1 Y Y Y Y N 5-76
H55 Deceleration Time (Jogging) 0.00 to 6000 s Y Y *1 Y Y Y Y N 5-197
H56 Deceleration Time for Forced Stop 0.00 to 6000 s Y Y *1 Y Y Y Y N
H57 1st S-curve acceleration range
(Leading edge)
0 to 100% Y Y 10 Y Y Y Y N
H58 2nd S-curve acceleration range
(Trailing edge)
0 to 100% Y Y 10 Y Y Y Y N
H59 1st S-curve deceleration range
(Leading edge)
0 to 100% Y Y 10 Y Y Y Y N
H60 2nd S-curve deceleration range
(Trailing edge)
0 to 100% Y Y 10 Y Y Y Y N
H61 UP/DOWN Control (Initial frequency
selection)
0: 0.00 Hz as default
1: Default is the frequency set by the last UP/DOWN command
immediately before the run command is turned off.
N Y 1 Y Y Y Y N
5-62
5-197
H63 Low Limiter (Mode selection) 0: Limit by F16 (Frequency limiter: Low) and continue to run
1: If the frequency lowers below the one limited by F16 (Frequency
limiter: Low), decelerate to stop the motor.
Y Y 0 Y Y Y Y N
5-93
5-198
H64 (Lower limiting frequency) 0.0: Depends on F16 (Frequency limiter, Low), 0.1 to 60.0 Hz Y Y 1.6 Y Y N N N 5-198
H65 Non-linear V/f Pattern 3 (Frequency) 0.0 (Cancel), 0.1 to 500.0 Hz N Y 0.0 Y Y N N N 5-72
H66 (Voltage) 0 to 240 V: Output an AVR-controlled voltage (for 200 V class series)
0 to 500 V: Output an AVR-controlled voltage (for 400 V class series)
N Y2 0 Y Y N N N
5-198
*1 6.00 s for inverters with a capacity of 22 kW or below; 20.00 s for those with 30 kW or above
*2 The factory default differs depending upon the inverter's capacity. See Table 5.2-17.
*6 The motor parameters are automatically set, depending upon the inverter's capacity. See Table 5.2-18.
*7 0.0 (Cancel) for inverters with a capacity of 22 kW or below; 5.0 Hz for those with 30 kW or above.
*8 0 V for inverters with a capacity of 22 kW or below; 20 V or 40 V for 200 V or 400 V class series of inverters with 30 kW or
above