5.2 Function Code Tables
5-12
Table 5.2-8
P codes: Motor 1 Parameters
Drive control
Code Name Data setting range
Change
when
running
Data
copying
Default
setting
V/f
PG
V/f
w/o
PG
w/
PG
To rq ue
control
Refer to
page:
P01 Motor 1 (No. of poles) 2 to 22 poles N Y1, Y2 4 Y Y Y Y Y 5-175
P02 (Capacity) 0.01 to 1000 kW (when P99 = 0, 2 to 4)
0.01 to 1000 HP (when P99 = 1)
N Y1, Y2 *6 Y Y Y Y Y
P03 (Rated current) 0.00 to 2000 A N Y1, Y2 *6 Y Y Y Y Y 5-176
P04 (Auto-tuning) 0: Disable
1: Tune while the motor stops. (%R1, %X and rated slip frequency)
2: Tune the motor while it is rotating under V/f control (%R1, %X and
rated slip frequency, no-load current, magnetic saturation factors 1
to 5, magnetic saturation extension factors "a" to "c")
3: Tune the motor while it is rotating under vector control (%R1, %X
and rated slip frequency, no-load current, magnetic saturation
factors 1 to 5, magnetic saturation extension factors "a" to "c";
enabled under vector control only)
N N 0 Y Y Y Y Y 5-177
P05 (Online tuning) 0: Disable 1: Enable Y Y 0 Y N N N N 5-178
P06 (No-load current) 0.00 to 2000 A N Y1, Y2 *6 Y Y Y Y Y
P07 (%R1) 0.00 to 50.00% Y Y1, Y2 *6 Y Y Y Y Y
P08 (%X) 0.00 to 50.00% Y Y1, Y2 *6 Y Y Y Y Y
P09 (Slip compensation gain for driving) 0.0 to 200.0% Y* Y 100.0 Y Y Y Y N 5-179
P10 (Slip compensation response time) 0.01 to 10.00 s Y Y1, Y2 0.12 Y Y N N N
P11 (Slip compensation gain for braking) 0.0 to 200.0% Y* Y 100.0 Y Y Y Y N
P12 (Rated slip frequency) 0.00 to 15.00 Hz N Y1, Y2 *6 Y Y Y Y N
P13 (Iron loss factor 1) 0.00 to 20.00% Y Y1, Y2 *6 Y Y Y Y Y
P14 (Iron loss factor 2) 0.00 to 20.00% Y Y1, Y2 0.00 Y Y Y Y Y
P15 (Iron loss factor 3) 0.00 to 20.00% Y Y1, Y2 0.00 Y Y Y Y Y
P16 (Magnetic saturation factor 1) 0.0 to 300.0% Y Y1, Y2 *6 Y Y Y Y Y
P17 (Magnetic saturation factor 2) 0.0 to 300.0% Y Y1, Y2 *6 Y Y Y Y Y
P18 (Magnetic saturation factor 3) 0.0 to 300.0% Y Y1, Y2 *6 Y Y Y Y Y
P19 (Magnetic saturation factor 4) 0.0 to 300.0% Y Y1, Y2 *6 Y Y Y Y Y
P20 (Magnetic saturation factor 5) 0.0 to 300.0% Y Y1, Y2 *6 Y Y Y Y Y
P21 (Magnetic saturation extension factor
"a")
0.0 to 300.0%
Y Y1, Y2 *6 Y Y Y Y Y
P22 (Magnetic saturation extension factor
"b")
0.0 to 300.0%
Y Y1, Y2 *6 Y Y Y Y Y
P23 (Magnetic saturation extension factor
"c")
0.0 to 300.0%
Y Y1, Y2 *6 Y Y Y Y Y
P53 (%X correction factor 1) 0 to 300% Y Y1, Y2 100 Y Y Y Y Y 5-180
P54 (%X correction factor 2) 0 to 300% Y Y1, Y2 100 Y Y Y Y Y
P55 (Torque current under vector control) 0.00 to 2000 A N Y1, Y2 *6 N N Y Y Y
P56 (Induced voltage factor under vector
control)
50 to 100%
N Y1, Y2 *6 N N Y Y Y
P57 Reserved *9 0.000 to 20.000 s Y Y1, Y2 *6 - - - - Y
P99 Motor 1 Selection 0: Motor characteristics 0 (Fuji standard motors, 8-series)
1: Motor characteristics 1 (HP rating motors)
2: Motor characteristics 2 (Fuji motors exclusively designed for vector
control)
3: Motor characteristics 3 (Fuji standard motors, 6-series)
4: Other motors
N Y1, Y2 0 Y Y Y Y Y 5-180
Table 5.2-9
H codes: High Performance Functions
Drive control
Code Name Data setting range
Change
when
running
Data
copying
Default
setting
V/f
PG
V/f
w/o
PG
w/
PG
To rq ue
control
Refer to
page:
H03 Data initialization 0: Manually set value
1: Initialize all function code data to the factory defaults
2: Initialize motor 1 parameters
3: Initialize motor 2 parameters
4: Initialize motor 3 parameters
5: Initialize motor 4 parameters
N N 0 Y Y Y Y Y 5-181
H04 Auto-reset (Times) 0: Disable; 1 to 10: Auto-reset times Y Y 0 Y Y Y Y Y 5-182
H05 (Restart time) 0.5 to 20.0 s Y Y 5.0 Y Y Y Y Y
H06 Cooling fan ON/OFF control 0: Disable (Always in operation)
1: Enable (ON/OFF controllable)
Y Y 0 Y Y Y Y Y 5-183
H07 Curvilinear acceleration/deceleration 0: Disable (Linear ACC/DEC)
1: S-curve DEC (Weak)
2: S-curve DEC (Arbitrary, according to H57 to H60 data)
3: Curvilinear acceleration/deceleration
Y Y 0 Y Y Y Y N 5-76
5-183
H08 Rotational direction limitation
0: Disable
1: Enable (Reverse rotation inhibited)
2: Enable (Forward rotation inhibited)
N Y 0 Y Y Y Y N 5-184
The shaded function codes ( ) are applicable to the quick setup.
*6 The motor rated current is automatically set, depending upon the inverter's capacity. See Table 5.2-18.
*9 These function codes are reserved for particular manufacturers. Do not access these function codes.