5.4 Details of Function Codes
5-120
Discharging capability (F50)
The discharging capability refers to kWs allowable for a single braking cycle, which is obtained based on the
braking time and the motor rated capacity.
Table 5.4-58
Data for F50 Function
0
For the braking resistor built-in type
1 to 9000
1 to 9000 (kWs)
OFF
Disable the electronic thermal overload protection
2
=
(kW)capacity rated Motor × (s) time Braking
(kWs) capability gDischargin
(1)
(kW)capacity rated Motor(s) time Braking (kWs) capability gDischargin ×=
(2)
When the F50 is set to "0" (For the braking resistor built-in type), no specification of the
discharging capability is required.
Allowable average loss (F51)
The allowable average loss refers to a tolerance for motor continuous operation, which is obtained based on
the %ED (%) and motor rated capacity (kW).
Table 5.4-59
Data for F51 Function
0.001 to 99.99
0.001 to 99.99 (kW)
2
(kW)capacity rated Motor×
100
(%)%ED
=(kWs) loss average Allowable
(3)
(kW)capacity rated Motor×
100
(%)%ED
=(kWs) loss average Allowable
(4)
Resistance (F52)
F52 specifies the resistance of the braking resistor.