5.4 Details of Function Codes
5-142
Explanations of each function are given in normal logic system "Active ON."
Table 5.4-75
Data Control Method
Active
ON
Active
OFF
Defined Functions Signal Name
V/f
PG
V/f
PG
Less
PG
Torque
Control
Related
Function
Code/
Related Signal
(Data)
0 1000 Running RUN
{
{
{ { {
1 1001 Frequency (speed) arrival FAR
{
{
{ {
X E30
2 1002 Frequency (speed) detected FDT
{
{
{ { {
E31, E32
3 1003 Stopping due to undervoltage LU
{
{
{ { {
4 1004 Torque polarity detected B/D
{
{
{ { {
5 1005 Inverter output limiting IOL
{
{
{ { {
6 1006
Auto-restarting after momentary
power failure
IPF
{
{
{ { {
F14
7 1007 Motor overload early warning OL
{ { { { {
E34
, F10,
F12
8 1008 Keypad operating KP
{
{
{ { {
10 1010 Inverter ready output RDY
{
{
{ { {
11 -
Switch between commercial
power/inverter operation
(Magnetic contactor at commercial
power supply side)
SW88
{ {
XX X
12 -
Switch between commercial
power/inverter operation
(For inverter output side)
SW52-2
{ {
XX X
13 -
Switch between commercial
power/inverter operation
(For inverter output side)
SW52-1
{ {
XX X
E01 to E09
ISW50 (40)
ISW60 (41)
J22
15 1015
AX terminal function
(
For magnetic contactor at inverter input
side
)
A
X
{ { { { {
16 1016 Shifting to pattern operation stage TU
{ { { {
X
17 1017 Pattern operation cycle complete TO
{ { { {
X
18 1018 Pattern operation stage No. 1 STG1
{ { { {
X
19 1019 Pattern operation stage No. 2 STG2
{ { { {
X
20 1020 Pattern operation stage No. 4 STG4
{ { { {
X
22 1022
Inverter output limiting
(With delay)
IOL2
{ { { { {
IOL (5)
25 1025 Cooling fan ON/OFF control FAN
{
{
{ { {
H06
26 1026 Retrying TRY
{
{
{ { {
H04, H05
27 1027 Universal DO U-DO
{
{
{ { {
28 1028 Cooling fin overheat early warning OH
{
{
{ { {
29 1029 Simultaneous complete signal SY X
{
X
{
X
For details,
see the PG
Interface
Card
Instruction
Manual.
30 1030 Lifetime warning LIFE
{
{
{ { {
H42
31 1031 Frequency (speed) detected 2 FDT2
{ { { { {
E32, E36
33 1033 Command loss detected REF OFF
{
{
{ { {
E65
35 1035 Inverter outputting RUN2
{
{
{ { {
RUN (0)
36 1036 Under overload prevention control OLP
{
{
{ {
X H70

Table of Contents