5.4 Details of Function Codes
5-157
Chapter 5 Function Code
Details of
Function Codes
F codes
E40 to E43
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
E43
LED Monitor (Display Select) Related Function Code: E48 LED Monitor Details (Speed
Monitor Select)
This function selects the monitoring information of operation status displayed by the keypad LED.
Selecting the speed monitor with E43 provides a choice of speed-monitoring formats selectable with E48
(LED Monitor Details).
Table 5.4-82
Monitor Item
Display
Sample
LED Indicator Unit Meaning of Displayed Value
E43
data
Speed monitor With the function code E48, selecting following display form is possible. 0
Output frequency 1
(before slip
compensation)
5*00
Hz -> A
-> kW
Hz Display value = Output frequency (Hz) (E48 = 0)
Output frequency 2
(after slip
compensation)
5*00
Hz -> A ->
kW
Hz Display value = Output frequency (Hz) (E48 = 1)
Set frequency
5*00
Hz -> A
-> kW
Hz
Display value = Set frequency (Hz)
(E48 = 2)
Motor speed
1500
Hz -> A ->
kW
r/min
Display value =
P01
120
×(Hz)frequency Output
(E48 = 3)
Loaded rotation
speed
30*0
Hz -> A ->
kW
r/min
Display value = Output frequency (Hz)
x E50
(E48 = 4)
Line speed
30*0
Hz -> A ->
kW
m/min
Display value = Output frequency (Hz)
x E50
(E48 = 5)
Speed (%)
5*0
Hz -> A ->
kW
%
Display value =
100×
frequency Maximum
frequency Output
(E48 = 7)
Output current
1"34
Hz -> A ->
kW
A Inverter output current effective value 3
Output voltage
200u
Hz -> A ->
kW
V Inverter output voltage effective value 4
Calculated torque
50
Hz -> A ->
kW
%
Motor output torque (Calculated
value)
8
Power consumption
1*25
Hz -> A ->
kW
kW Inverter input power value 9
PID command
1*0*
Hz -> A ->
kW
- 10
PID feedback value
)0*
Hz -> A ->
kW
-
PID command value or PID feedback
value is converted into a physical
quantity of the object to be controlled
and displayed
See the function codes E40 and E41.
12
PID output
10**
Hz -> A ->
kW
%
Displays PID output in % as the
maximum output frequency (F03)
being at 100%
14
Load factor
50;
Hz -> A ->
kW
%
Displays load factor of the motor in %
as the rated output being at 100%
15
Motor output
)85
Hz -> A ->
kW
kW Motor output (kW) 16
Analog input monitor
8"00
Hz -> A ->
kW
-
An analog input to the inverter is
converted to a desired format and
displayed.
See the function codes E40 and E41.
17
Torque current
48
Hz -> A ->
kW
%
Displays torque current command
value or calculated torque current
23
Magnetic flux command
value
50
Hz -> A ->
kW
%
Displays magnetic flux command
value
(Available under vector control)
24
Integral power
consumption
10*0
Hz -> A ->
kW
kWh
Display value =
100
(kWh) nconsumptio power Integral
25
Light on, Light off