5.4 Details of Function Codes
5-170
Pattern operation (operation selection) (C21)
The next operation pattern can be selected.
Table 5.4-96
C21: Setting Value Operation Pattern
0 Perform a pattern operation cycle, then stop operation
1 Perform pattern operation repeatedly. Immediate operation stop by stop command.
2 Perform one cycle of pattern operation cycle, then continue operation with the last
frequency set.
Fig. 5.4-77
When a pattern operation is started with C21 = 0 and the FWD (REV) terminal = ON, the motor
stops after the final stage completes even the FWD (REV) terminal is remained ON.
At this time, when the values of F01 and/or C30 is changed or ON/OFF status of the control
terminal "Hz2/Hz1" is switched without turning off the FWD (REV) terminal, the operation
immediately resumes according to the changed set frequency.
An accident or injuries could occur.
Pattern operation (Stage 1 to Stage 7 operation time) (C22 to C28)
Set the operation time of stage 1 to 7.
Set 0 to the operation time of the stage, which is not used. Set 00. The stage is skipped and shifted to the
next stage.
- Data setting range: 0.0 to 6000 (s)