11.4 Option
11-96
Function codes dedicated to SX-bus communication card
Table 11.4-68
No. Name
Data setting
range *1
Function
y98
Select run/frequency
command sources
0 to 3 Select from the following choices:
Table 11.4-69
y98
Frequency
command
source
Run command
source
0 Inverter Inverter
1 SX bus Inverter
2 Inverter SX bus
3 SX bus SX bus
0, 4 to 9 Immediately coast to a stop and trip with
er5
.
1
After the time specified by o28, coast to a stop
and trip with
er5
.
2
If the communications link is restored within
the time specified by o28, ignore the
communications error. If a timeout occurs,
coast to a stop and trip with
er5
.
3, 13 to 15
Keep the current operation, ignoring the
communications error.
(No trip with
er5
.)
10
Immediately decelerate to a stop. Trip with
er5
after stopping.
11
After the time specified by o28, coast to a stop
and trip with
er5
after stopping.
o27
Select error processing for
SX-bus network breaks
12
If the communications link is restored within
the time specified by o28, ignore the
communications error. If a timeout occurs,
decelerate to a stop and trip with
er5
.
o28
Set the operation timer to be
used in error processing for
SX-bus network breaks
0.0 to 60.0 sec
Timer operation time for setting o27 = 1, 2, 11,
or 12
0 Standard format o30
Select communications
format of SX-bus
communications card
1 to 255
Specification not allowed
*1
The underlined
value are factory defaults.