13.1 Compliance with UL Standards and Canadian Standards (cUL certification)
13-4
Conformity with UL Standards and Canadian Standards (cUL certification) (cont.)
Required torque
lb-in (N・m)
Wire size AWG (mm
2
)
Main terminal Cu Wire
L1/R, L2/S, L3/T U, V, W P1, P(+)
Power supply voltage
Nominal applied motor
Inverter type
HD/MD/LD mode
Class J fuse size (A)
Circuit breaker trip size (A)
Main terminal
Aux. control power supply
Aux. fan power supply
60ºC wire
75ºC wire
Remarks
60ºC wire
75ºC wire
Remarks
75ºC wire
Remarks
Aux. control power supply
Aux. fan power supply
0.4 FRN0.4G1-4J
3
0.75 FRN0.75G1-4J
6
5
10.6
(1.2)
- -
1.5 FRN1.5G1-4J
10 10
2.2 FRN2.2G1-4J
15 15
3.7 FRN3.7G1-4J
HD
20 20
15.9
(1.8)
14
(2.1)
14
(2.1)
*1
14
(2.1)
14
(2.1)
*1
5.5
HD 30 30
12
(3.3)
FRN5.5G1-4J
LD
7.5
HD
40 40
10
(5.3)
12
(3.3)
FRN7.5G1-4J
LD
11
HD
60 50
10
(5.3)
FRN11G1-4J
LD
30.9
(3.5)
-
8
(8.4)
*1
*2
*3
-
8
(8.4)
*1
*2
*3
15
HD
70 60
FRN15G1-4J
LD
18.5
HD
90 75
6
(13.3)
FRN18.5G1-4J
LD
22
HD
100 100
4
(21.2)
6
(13.3)
6
(13.3)
FRN22G1-4J
LD
51.3
(5.8)
4
(21.2)
6
(13.3)
30
HD
125
3
(26.7)
4
(21.2)
FRN30G1-4J
LD
37
HD
175
125
2
(33.6)
3
(26.7)
-
FRN37G1-4J
LD
45
HD
200 150
2
(33.6)
2
(33.6)
-
FRN45G1-4J
LD
55
HD
200
2
(33.6)
-
-
FRN55G1-4J
LD
119.4
(13.5)
-
1/0
(53.5)
1/0
(53.5)
-
75
HD
250
175
2/0
(67.4)
FRN75G1-4J
LD
90
HD
300 200
2/0
(67.4)
4/0
(107.2)
4/0
(107.2)
FRN90G1-4J
MD/LD
110
HD
350 250
1/0×2
(53.5×2)
2/0×2
(67.4×2)
FRN110G1-4J
MD/LD
238.9
(27)
132
HD
400 300
1/0×2
(53.5×2)
2/0×2
(67.4×2)
3/0×2
(85×2)
FRN132G1-4J
MD/LD
160
HD
500 350
3/0×2
(85×2)
3/0×2
(85×2)
4/0×2
(107.2×2)
FRN160G1-4J
MD/LD
200
HD
600
4/0×2
(107.2×2)
250×2
(127×2)
300×2
(152×2)
FRN200G1-4J
MD/LD
Three-phase 400V
220
FRN220G1-4J
HD
700
500
424.7
(48)
10.6
(1.2)
10.6
(1.2)
-
250×2
(127×2)
*2
*3
-
300×2
(152×2)
*2
*3
350×2
(177×2)
*2
*3
14
(2.1)
*1
*2
14
(2.1)
*1
*2
(Note) Control circuit terminals Tightening torque: 6.1 lb-in (0.7 N・m), recommended wire size: AWG18 (0.8 mm
2
)
(Note) A box () in the above table replaces an alphabetic letter depending on the type.
*1 No terminal end treatment is required for connection.
*2 Use 75°C Cu wire only.
*3 The wire size of UL Open Type and Enclosed Type are common. Please contact us if UL Open Type exclusive wire is
necessary.
(To be continued)