Example:
CC 19200,0,1,1
Configure auxiliary communication port for 19200 baud, no handshake, general
port mode and echo turned on.
RS-422 Configuration
The DMC-40x0 can be ordered with the main and/or auxiliary port configured for RS-422 communication. RS-422
communication is a differentially driven serial communication protocol that should be used when long distance
serial communication is required in an application.
RS-422-Main Port (Non-Standard Option)
Standard connector and cable when DMC-40x0 is ordered with RS-422 Option.
Pin Signal
1 RTS-
2 TXD-
3 RXD-
4 CTS-
5 GND
6 RTS+
7 TXD+
8 RXD+
9 CTS+
RS-422-Auxiliary Port (Non-Standard Option)
Standard connector and cable when DMC-40x0 is ordered with RS-422 Option.
Pin Signal
1 CTS-
2 RXD-
3 TXD-
4 RTS-
5 GND
6 CTS+
7 RXD+
8 TXD+
9 RTS+
Ethernet Configuration
Communication Protocols
The Ethernet is a local area network through which information is transferred in units known as packets.
Communication protocols are necessary to dictate how these packets are sent and received. The DMC-40x0
supports two industry standard protocols, TCP/IP and UDP/IP. The controller will automatically respond in the
format in which it is contacted.
DMC-40x0 User Manual Chapter 4 Software Tools and Communication 50