Example 1:
Application of 2 VRRs (1A rated) with direct paralleling
RL = 50m 2.5mm
2
Cu = 0.37Ω
RLDC = 0.007Ω
X =
R
L
RLDC'
<0.0526 where R
LDC'
= R
LDC
+ R
3
R
LDC
' > 19R
L
R
LDC
' > 7.03
Therefore:
RS > 7.03 – 0.007
> 7.023
Choose a value of Rs = 7Ω.
Required continuous rating = 2In = 2A
Therefore required continuous power rating of RS = 28W.
Allowing a minimum power derating of 50%= 56W, use a resistor rated at 75W.
Therefore use RS = 7 Ω 75W
Note: RS should withstand the maximum main CT secondary rms current for a minimum
of three seconds. The maximum output of the main CTs should not exceed three times
the steady state current through its connected burden and CT resistance to cause
saturation.