VLT
®
5000 Series
VLT 5000 Series protection:
Electronic motor thermal protection against overload.
Temperature monitoring of heat-sink ensures that the VLT frequency converter cuts out if the temperature
reaches 90
C for IP 00 and IP 20. For IP 54, the cut-out temperature is 80
C. An overtemperature can only
be reset when the temperature of the heat-sink has fallen below 60
C.
The VLT frequency converter is protected against short-circuiting on motor terminals U, V, W.
The VLT frequency converter is protected against earth fault on motor terminals U, V, W.
Monitoring of the intermediate circuit voltage ensures that the VLT frequency converter cuts out if the inter-
mediate circuit voltage gets too high or too low.
If a motor phase is missing, the VLT frequency converter cuts out, see parameter 234 Motor phase monitor.
If there is a mains fault, the VLT frequency converter is able to carry out a controlled deramping.
If a mains phase is missing, the VLT frequency converter will cut out when a load is placed on the motor.
MG.51.A1.02 - VLT is a registered Danfoss trade mark
13
Technical data