VLT
®
5000 Series
■ Installation of VLT 5008-5027 200-240V, VLT
5016-5062 380-500 V CompactIP 20 and IP 54
Cooling
All Compact units in the above-mentioned series re-
quire a minimum space of 200 mm above and below
the enclosure and must be installed on a plane, ver-
tical surface (no spacers). This applies to both IP 20
and IP 54 units.
Side-by-side
Compact IP 20
Compact IP 54 (flange-by-flange)
All IP 20 and IP 54 units in the above-mentioned se-
ries can be installed side by side without any space
between them, since these units do not require cool-
ing on the sides.
MG.51.A1.02 - VLT is a registered Danfoss trade mark
44