11 Commissioning
PHLOX - Ignition Control System 93
11.4 Ignition start
When the engine is started, the ignition can be set up to start in 2 different ways:
Start-type 1 (Par. 250 = 1):
When configured as start-type 1, ignition begins as soon as speed (Par. 2000) exceeds
StartSpeed1 (Par. 255).
Start-type 2 (Par. 250 = 2):
When configured as start-type 2, ignition begins when speed (Par. 2000) exceeds
StartSpeed1 (Par. 255) and after the StartDuration1 delay (Par. 265) or when speed ex-
ceeds StartSpeed2 (Par. 256) immediately.
Speed
Time
StartSpeed1
Par. 255
Ignition
stop
Ignition
start
StartSpeed2
Par. 256
Speed
Time
StartSpeed1
Par. 255
Ignition
stop
Ignition
start
StartDuration1
Par. 265

Table of Contents