14 Error Handling
212 PHLOX II Ignition Control System
ECU page is faulty
- The data sectors reserved for control device identification are faulty.
Error message only, data used on.
NMI page is faulty
- The data sectors reserved for NMI data (e.g., seconds of operation) is
faulty.
Error message only, data used on.
Work data page is faulty
- The data sectors reserved for operational data are faulty.
Error memory is cleared, other data is used on.
Table 42: Possible errors: Data memory
14.4.13 Configuration
3092 ErrConfiguration
Configuration error
- At least one configuration of the control device is faulty.
Error message only
The configuration error is shown in parameter 3000 ConfigurationError.
Check and correct faulty configuration.
Table 43: Possible errors: Configuration
14.4.14 Internal computing error
3094 ErrIntern
Stack overflow
- The memory reserved for the stack is full.
Emergency shutdown
Write down parameters 3191 to 3199.
Restart governor by a reset and inform HEINZMANN.